EMT conduit-fill helper for common THHN/THWN copper conductor sizes. This version uses the real NEC fill-percentage rule set and published EMT conduit-fill counts for more than two conductors.
| Code authority | NEC Chapter 9 Table 1 fill rules: 53% for 1 conductor, 31% for 2, 40% for over 2. |
|---|---|
| Practical table basis | Published EMT THHN/THWN conduit-fill charts corresponding to NEC Table C style counts for more than two conductors. |
| What this version does | Exact count check for EMT with more than two same-size THHN/THWN conductors. |
| What this version does not do yet | Exact one- and two-conductor area math, mixed conductor sizes, or full raceway-type coverage. |
| Trade size | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 3 AWG | 2 AWG | 1 AWG | 1/0 | 2/0 | 3/0 | 4/0 | 250 | 300 | 350 | 400 | 500 |
|---|
This table is included so the page remains transparent and auditable. The comparison result comes directly from the selected row and conductor size.